In article
Mike Ruskai
> My plan is to run one length of 6/3 from a 40A or 50A double breaker
> at the main panel to the subpanel, using buried PVC conduit for the
> outside portion.
In article
clare at wrote:
> Sure looks like he's running 220, or he would not be running 6/3 wire.
> Which also answers the question if he is running 3 plus ground or 4.
> 6/3 will have red, white, black, and bare wires.
Since he is planning on using a "Double Breaker, in his Main Panel,
to feed the Sub-Panel in the "New Shed", most folks would "Assume"
that he would be feeding 240Vac SinglePhase thru the conduit, which
if PVC, would require 3 Ea. #6 Wires, plus a Ground.